Product · reference architecture

One cabinet. Cooling, distribution, leak detection — included.

SUPPLY 25–45 °CΔT ≈ 15 KRETURN ≤ 60 °C

Your liquid-ready servers slide in through ORv3-compatible blind-mate interfaces and universal UQD couplings. One sealed loop rejects heat to room air. Power and network are all a site provides.

FIG.3 — click parts

What's inside

FIG.3 — REFERENCE ARCHITECTURE (SCHEMATIC, NOT A PHOTOGRAPH) · CLICK PARTS
HEAT → ROOM AIR42U · L2A CLOSED LOOPCOLDLIQUID-READY SERVERCOLDLIQUID-READY SERVERCOLDLIQUID-READY SERVERCOLDLIQUID-READY SERVERCOLDLIQUID-READY SERVERYOUR SERVERS · SLIDE IN, BLIND-MATEMANIFOLDPUMP · FILTER · CTRLL2A HEAT OUT →PG25COOLANTUQDCOUPLINGSLEAKSENSORSNO FACILITYWATER

Click any part — cold plates, manifold, UQD couplings, L2A unit, loop, sensors — for what it is and why it’s specified that way.

Specification

Target specification

targets, verified on the demo unit before first delivery
COOLING CLASS20–50 kW IT load per cabinet (L2A closed loop, single loop per cabinet)
ROOM AIR ENVELOPEDesigned for 25–35 °C room air; capacity derates with temperature — envelope published, per-unit curve from sample testing
SERVER INTERFACESOCP ORv3-spec blind-mate manifold · UQD quick disconnects · any OEM DLC server
HEAT CAPTUREDirect-to-chip share 60–80% (server-dependent); air share absorbed by the cabinet loop
ROOM REQUIREMENTAC able to extract ≥ 1.1 × full IT load; standard single- or three-phase power; no water, no construction
COOLANTPG25 water-glycol, PFAS-free, factory-sealed loop
MONITORINGLoop temperature/pressure, leak sensors, remote telemetry with alarms
FORM42U sealed enclosure · delivered as one unit · commissioning in days

Rows marked as envelopes are planning-grade physics from our published derivations — not yet per-unit certified curves. Final specifications accompany the engineering review of your configuration.

Honest engineering notes

The three things we will always say out loud

Heat goes to the room

L2A moves heat into room air; the building extracts it. We size the room first — the worksheet is public.

Capacity derates

At 35 °C room air an L2A loop delivers roughly half its 25 °C capacity. Any vendor not showing you this curve is hiding it — ours is public.

Leak risk is managed

Water-based loop leak risk is engineered down, not denied: sealed loop, UQD self-sealing couplings, sensors and telemetry. Derivation public.

Size it for your loadSee it in a hospital